Philippi Academy

Calibrate battery monitor: Capacity, Peukert, Synchronisation

8 min read
Answered briefly

Four values determine the accuracy: the nominal capacity of the entire battery bank, the Peukert exponent (around 1.1 to 1.25 for lead, close to 1.0 for LiFePO4), the charging efficiency (around 90 percent for lead, about 99 for LiFePO4), and the synchronization thresholds. Without regular full charging, the display will drift regardless of the settings.

A battery monitor does not measure the state of charge. It counts ampere-hours and calculates a percentage value from this. For this value to be accurate, four settings must match the installed battery bank, and the counter must regularly receive a known reference point. This article covers both in the correct order.

Why the display needs to be maintained

The monitor forms an integral: it adds every ampere-hour flowed in and subtracts every ampere-hour drawn out. An integral has no absolute reference — it only knows changes. Every small measurement error, every current that flows past the shunt, and every deviation in the calculation parameters therefore add up instead of balancing each other out.

The reference point is full charge. If the monitor detects it, it sets the counter to 100 percent and starts over. Everything that happens between two full charges is calculated.

Step 1: Capacity

The nominal capacity of the entire battery bank in ampere-hours, not that of a single battery, must be entered. Three parallel 100 Ah batteries result in 300 Ah. In contrast, for series connection to a higher voltage, the capacity remains that of a single battery.

Two points are often done incorrectly here. Firstly, the usable capacity is entered instead of the nominal capacity — but the monitor calculates with the nominal value and derives the depth of discharge itself. Secondly, the value remains unchanged after a battery replacement. An aged battery bank actually has less capacity; this is a reason to correct the value downwards after a few years based on a capacity test, but not a reason to estimate it arbitrarily.

Step 2: Peukert Exponent

Lead-acid batteries deliver less capacity at high discharge currents than at low ones. The Peukert exponent represents this relationship. The higher the value, the stronger the dependence on the current.

Technology Typical Range Practical Significance
LiFePO4 1.00 to 1.05 Capacity almost independent of current
AGM approx. 1.1 noticeable dependence at high currents
Gel approx. 1.1 to 1.2 like AGM, somewhat more pronounced
Flooded battery approx. 1.2 to 1.25 strong dependence, great significance

Guideline values for onboard applications. If the manufacturer states its own value or two capacity specifications at different discharge times, this information takes precedence — the exponent can also be calculated directly from two such value pairs.

If unsure, leave the default value of the device for lead-acid and enter a value close to 1.0 for LiFePO4. A Peukert exponent that is too high for a lithium battery bank will cause the display to drop under load and then seemingly recover — behavior that is regularly mistaken for a battery fault.

Step 3: Charge Efficiency

More charge goes in during charging than comes out later. The difference is converted into heat and, in the case of lead, into side reactions. The charge efficiency reflects this: for lead, it is in the order of 90 percent, for LiFePO4 close to 99.

If this value is set too high, the monitor reports the battery bank as full too early, and the display drifts upwards over the weeks. If it is set too low, the battery bank appears permanently emptier than it is.

Step 4: Synchronization Thresholds

For the monitor to recognize a full charge, three conditions must be met simultaneously: the voltage must be above a set charge termination voltage, the charging current must have fallen below a small residual value, and both must persist for a minimum period.

The charge termination voltage must be just below what the charger actually achieves — otherwise, it will never be exceeded, and no synchronization will ever occur. The residual current is usually specified as a percentage of capacity and is in the range of a few percent; for a 300 Ah battery bank, this is roughly a few amperes. The minimum time prevents a brief voltage peak from being interpreted as a full charge.

NoteWith LiFePO4, this detection is more delicate than with lead-acid, because the charging current remains high almost until the end and then drops very quickly. If the windows are set too narrowly here, no synchronization will occur for days. When in doubt, set the charge termination voltage a little lower and the minimum time rather short.

Entwicklung philippi — Entwicklungsabteilung, philippi elektrische systeme GmbH

Verfasst und fachlich geprüft von der Entwicklungsabteilung der philippi elektrische systeme GmbH in Remseck am Neckar. Ändert sich eine Norm oder eine Produktspezifikation, wird der Beitrag überarbeitet und das Prüfdatum aktualisiert.

Entwicklung, Fertigung und Prüfung von Bordnetzkomponenten seit über vierzig Jahren

Erstellt 16.09.2026 · Zuletzt geprüft 09.09.2026

Was this post helpful?

Something is missing