Planning and setting up the PSU: channels, current limit, dimming, H-bridge
In short
The PSU 9012-8 ADV distributes 70 A continuously (90 A for one minute) across eight channels with up to 20 A each, outputs 7 and 8 up to 25 A. The current limit of each output is set in 5 A steps and replaces the fuse: above the inrush current of the load, below the capacity of the cable. Dimming suits approved LED lighting, and the H-bridge drives motors and valves in both directions.
This product help collects the guides for the philippi PSU 9012-8 ADV, the digital power distribution: how the channels are assigned to loads, how the current limit is set for each output, when dimming, flashing and timers make sense, how the H-bridge drives motors and valves and how several units work together. What the PSU does in the on-board network is shown on the page Dimming lights and digital switching with the PSU; the basics of cable cross-section and protection are in the topic area Distribute and Secure.
Planning channels
The PSU 9012-8 ADV has eight channels and carries 70 A total current continuously, 90 A for one minute; each output takes up to 20 A, outputs 7 and 8 up to 25 A. Plan in this order: number of channels, realistic simultaneous load against the 70 A, then the largest single load per channel including inrush current. Dimmable circuits and H-bridge outputs are assigned first. For 24 V systems there are the 5024-8 ADV with 50 A and the 10024-8 ADV with 100 A total current.
Current limit instead of a fuse
Each output can be limited in 5 A steps, on the 9012-8 ADV from 5 to 20 A and up to 25 A on outputs 7 and 8; the limit replaces the fuse of the circuit. The value lies above the inrush current of the load and below the current-carrying capacity of the installed cable. If no value fits in between, the cross-section is too small.
Dimming, flashing, timers and H-bridge
Dimming works by switching the output on and off rapidly; this suits LED lighting approved for it, not electronics with their own power supply. The integrated H-bridge reverses polarity and drives steps, motorised valves, actuators and flaps in both directions without two changeover relays. If the channels or current of one unit are not enough, several PSUs are operated in series or in parallel; supply cable and main fuse are then recalculated.
Michael Kögel · Managing Director, philippi elektrische systeme GmbH
Michael Kögel is Managing Director of philippi elektrische systeme GmbH in Remseck am Neckar. Since 1978, the family-owned company has developed and manufactured on-board electrical systems for yachts, motorhomes and special vehicles.
Diplom-Ingenieur (Dipl.-Ing.), electrical engineering, with philippi for more than 35 years. Articles in the philippi Academy are written together with the engineering department and technically reviewed.
Published · Last reviewed
5 articles
Articles. In this subject area.
Combining Multiple PSU Units: Series, Parallel, Total Current
Multiple PSU units can be operated in series or in parallel. Before arranging them, the question of the bottleneck arises: a lack of channels...
5 minReadControl motors, valves, and footpegs via the H-bridge
The integrated H-bridge of the PSU reverses the polarity at the output, thereby controlling DC drives in both directions—electric steps, motor valves, actuators, and...
6 minReadDimming, flashing, timer: using the PSU's relay functions
The PSU supports dimming, flashing, and timer control per output, as well as rule-based sequences including master light and panic functions. Dimming is achieved...
6 minReadSet current limit per channel: from 5 to 25 Amperes
The current limit of each PSU output can be set in 5 A increments — on the 9012-8 ADV from 5 to 20 A,...
6 minReadPlan PSU 9012-8: Distribute outputs to loads
The PSU 9012-8 ADV has eight channels, handles a total current of 70 A continuously (90 A for one minute) and up to 20...
6 minReadRelated topics
Matching products. Order directly.
Related. Related subject areas.
Distribute and Secure
Cable cross-sections, fuse ratings, and the construction of a distribution board — the calculation methods that turn a consumer list into a distribution.
ReadDigital onboard network
P-Bus, NMEA 2000, and Remote Access — Structure, Addressing, Termination, and What to Consider When Integrating Third-Party Devices.
ReadProduct help switch panels
Series 100, 200 or 700, circuits, monitor level, double-pole switching and outdoor installation: the guides for philippi switch panels.
ReadTechnical
Your case isn't covered?
Ask us.
Our team knows every component and usually replies on the same working day, by email or by phone.