With holder 110–200 A
Class-T 125 A
Fuse + holder
Class T fuse 125 A with matching fuse holder for 110 to 200 A.
121,35 € with holder Fuse 58,70 € + holder 62,65 €
Distribution and protection
A fuse protects the cable, not the device. Which type fits depends on two things: the rated current set by the cross-section, and the breaking capacity needed at the installation point. Directly at the battery, and especially at a lithium battery, only a few types are suitable.
20 kA Class T breaking capacity for lithium.
17.8 cm maximum unprotected from the positive terminal.
6 types from 3 A to 600 A.
Class T for lithium
With holder 110–200 A
Fuse + holder
Class T fuse 125 A with matching fuse holder for 110 to 200 A.
121,35 € with holder Fuse 58,70 € + holder 62,65 €
With holder 110–200 A
Fuse + holder
Class T fuse 200 A with matching fuse holder for 110 to 200 A.
121,35 € with holder Fuse 58,70 € + holder 62,65 €
Most frequently ordered
Fuse + holder 3/8"
Class T fuse 250 A with matching fuse holder for 225 to 400 A.
141,23 € with holder Fuse 58,70 € + holder 82,53 €
With holder 225–400 A
Fuse + holder 3/8"
Class T fuse 300 A with matching fuse holder for 225 to 400 A.
141,23 € with holder Fuse 58,70 € + holder 82,53 €
With holder 225–400 A
Fuse + holder 3/8"
Class T fuse 400 A with matching fuse holder for 225 to 400 A.
141,23 € with holder Fuse 58,70 € + holder 82,53 €
| Type | Typical range | Breaking capacity | Where |
|---|---|---|---|
| Blade fuse (ATO, FSL) | 3 to 25 A | approx. 1 kA | behind a distribution or panel, single consumers |
| MIDI strip fuse (STM) | medium current | see data sheet | chargers, DC-DC chargers, sub-distribution |
| MEGA fuse (FSM) | high current | at least 2 kA | inverters, main cables with lead, AGM, gel |
| Strip fuse (STS, ANL) | high current, holder up to 750 A | at least 2 kA | main protection with lead, AGM, gel |
| Terminal fuse SHB (MRBF) | 30 to 300 A | 10 kA | directly on the battery post, also with lithium |
| Class T | 110 to 600 A | 20 kA at 125 V DC | main fuse of large lithium banks |
These breaking capacity values are the ones the cable configurator uses to check whether a type may be installed at a given point. All high-current fuses with holders are under high-current protection, circuit breakers and consumer protection under consumer protection.
The fuse rating always lies between two limits: above the consumer's continuous current so it does not blow in operation, and below the cable's current-carrying capacity so the cable does not fail before the fuse. If you lay a thicker cable for voltage drop reasons, you still must not choose a larger fuse than the consumer requires.
The cable configurator calculates both in one step: cross-section by voltage drop and capacity, plus rating, fuse type and holder.
In a short circuit, a battery delivers many times its normal current. A fuse must not only detect this current but interrupt it safely. If it cannot, it keeps burning as an arc. That is why the blade fuse with about 1 kA does not belong on the battery post but behind a distribution that already limits the short-circuit current.
At the post of a lead, AGM or gel battery, types rated at 2 kA or more are needed: strip, MEGA and terminal fuses.
Lithium banks have very low internal resistance and deliver far higher short-circuit currents than lead batteries. At the post of a lithium battery, only the SHB terminal fuse with 10 kA and the Class T fuse with 20 kA are permitted. Class T starts at 110 A; below that, the SHB directly on the post is the choice.
The main fuse belongs as close as possible to the positive post, because the cable section before it is unprotected in a short circuit. ABYC E-11 gives 7 inches, i.e. 17.8 cm, as the limit. The cable configurator allows at most 20 cm and warns from 17.8 cm. The simplest solution is the SHB terminal fuse on the ABH 1 holder directly at the post.
Consumers behind the main fuse are protected individually at the switch panel or in a fuse block, each matching its cross-section.
A design with a high breaking capacity belongs on the terminal: for lead-acid, AGM and gel, strip, MEGA or bolt-on fuses from 2 kA; for lithium, only the SHB bolt-on fuse with 10 kA or Class T with 20 kA. Blade fuses manage around 1 kA and belong behind a distribution unit.
The cable cross-section. The rated current lies above the continuous current of the load, so that the fuse does not blow during operation, and below the current-carrying capacity of the cable. The fuse protects the cable; the device protects itself. A thicker cable chosen for voltage drop does not allow a larger fuse than the load requires.
Both are approved for lithium on the terminal. The SHB bolt-on fuse breaks 10 kA and covers 30 to 300 A; it sits compactly on the ABH holder directly on the terminal. Class T breaks 20 kA at 125 V DC, starts at 110 A and is the main fuse for large lithium banks and inverters.
A circuit breaker can be reset after tripping and can also serve as a switch. Fuses are cheaper and more compact but must be replaced after they blow. Spare fuses therefore belong on board. Circuit breakers for individual loads can be found in our category for load protection.
By Michael Kögel, Managing Director, philippi elektrische systeme GmbHPublished
Academy
From consumer current and cable ampacity to the correct rated value — with tripping characteristics, installation type, and the limits of common...
Why the main fuse belongs on the positive pole, what distances are permissible, and why breaking capacity becomes the decisive selection criterion...
The formula, both design criteria and ready-made tables for 12 V and 24 V — with the question of when voltage drop...
Checklist from the charge controller to the main fuse, in the order of procedure — including capacity calculation, the three conversion options,...
Advice
Describe your boat or vehicle to us and we will suggest the right components.