Distribute and protect power: Control panels, fuses, cross-sections

In short

The cable cross-section is determined by the current, double the cable length, and the permissible voltage drop: Cross-section = 2 × length × current × 0.0175 ÷ permissible voltage drop. ISO 13297:2020 allows 10 percent, and 3 percent for safety-critical circuits. The fuse protects the cable, never the device — its nominal value must not exceed the current carrying capacity of the cable.

Between the battery and the load, there are two questions that determine safety and functionality: how thick the cable must be, and what happens if it gets damaged. Both can be calculated. This section covers everything from cross-section and fuse protection to the final planning of the switch panel.

The cross-section follows the length, not the connector

A cable has resistance. If current flows through it, voltage drops, and the load receives less than what is at the battery. At 230 volts, this is hardly noticeable. At 12 volts, it is the determining factor for the entire design: a one-volt loss here is more than eight percent of the onboard voltage.

The second point, which is regularly overlooked: The total length of both ways counts. The current flows out via the positive cable and returns via the negative cable, and both paths generate a voltage drop. A load five meters away from the distribution point has a ten-meter cable run.

This leads to a rule that contradicts intuition: it is not the load that determines the cross-section, but the combination of current and distance. The same anchor winch in the bow requires a significantly thicker cable than the same winch located next to the battery.

The calculation

FormulaCross-section in mm² = (2 × cable length in m × current in A × 0.0175) ÷ permissible voltage drop in V

The factor 0.0175 is the specific resistance of copper in ohms times square millimeters per meter. It applies to room temperature; warm cables in the engine compartment have slightly higher resistance, which makes the calculation slightly conservative — which is intentional.

That leaves the question of what voltage drop is permissible. ISO 13297:2020 specifies two values: 10 percent of the nominal voltage for standard circuits, and 3 percent for safety-relevant ones — navigation lights, bilge blowers, bilge pumps. At 12 volts, these are 1.2 and 0.36 volts, respectively.

The difference is significant. For 20 A over a distance of 5 meters, the 3-percent design requires 10 mm², while the 10-percent design requires only 4 mm². Both can be correct — it depends on what is at the end of the line.

Cable configurator: calculate directly below using your values

The two tables show rounded standard sizes for selected currents and lengths. The cable configurator calculates exact values for your requirements — including fuse rating, fuse type, and a complete parts list for assembly.

Go to cable configurator

12 V, 3 percent voltage drop

Current 2 m 5 m 10 m 15 m
5 A 1.5 mm² 2.5 mm² 6 mm² 10 mm²
10 A 2.5 mm² 6 mm² 10 mm² 16 mm²
20 A 4 mm² 10 mm² 25 mm² 35 mm²
40 A 10 mm² 25 mm² 50 mm² 70 mm²
60 A 16 mm² 35 mm² 70 mm² 95 mm²
100 A 25 mm² 50 mm² 120 mm² 150 mm²

Distance measured one way, doubled in the calculation. Values rounded up to the next standard size. For non-critical loads with a 10 percent limit, the requirement is about one-third.

24 V, 3 percent voltage drop

Current 2 m 5 m 10 m 15 m
5 A 1.5 mm² 1.5 mm² 2.5 mm² 4 mm²
10 A 1.5 mm² 2.5 mm² 6 mm² 10 mm²
20 A 2.5 mm² 6 mm² 10 mm² 16 mm²
40 A 4 mm² 10 mm² 25 mm² 35 mm²
60 A 6 mm² 16 mm² 35 mm² 50 mm²
100 A 10 mm² 25 mm² 50 mm² 95 mm²

At the same current, the cross-section is halved compared to 12 V. At the same power, the current is additionally halved — in that case, the requirement is one-quarter. This is the actual argument for 24 V on large vessels.

Calculate cable cross-section: tables for 12 V and 24 V

The complete calculation with both design criteria, the difference between voltage drop and current-carrying capacity, and the question of which one prevails in an individual case.

Read more

Fuse protection: The fuse protects the wire

The most common misconception regarding fuse protection is to view the fuse as device protection. It is wire protection. Its task is to prevent a cable from getting so hot in the event of a fault that the insulation melts — with all the consequences that entails in a boat hull.

This leads to the only hard rule of circuit protection: The nominal current of the fuse must never exceed the current-carrying capacity of the protected cable. The upper limit is therefore set. The lower limit is determined by the load: the fuse must withstand the operating current, including start-up peaks, without tripping.

Start-up currents are addressed via the characteristic curve, not by using a higher nominal value. A slow-blow fuse bridges the inrush current of a pump, whereas an increased nominal value undermines the cable protection.

It should also be noted that the current-carrying capacity of a cable depends not only on the cross-section but also on the environment. The same cable can handle less current in an engine compartment than in a well-ventilated locker, and less when bundled than when laid individually.

Determine fuse size

How to determine the correct nominal value based on load current, cross-section, and routing method — including characteristics, types, and the limits of rules of thumb.

Read more

The main fuse belongs at the battery

A fuse only protects what is behind it. The cable before it is unprotected — and between the battery and the switch panel, this is the thickest cable in the ship, carrying the highest possible short-circuit current. If it chafes through, no fuse in the switch panel can do anything, because it is not even in the fault path.

This is why the main fuse is placed as close as possible to the positive terminal. ABYC E-11.12.1.1.1 specifies a limit of 175 millimeters from the connection point. If the cable is also in a protective conduit, up to 40 inches are allowed; for direct connection to the battery terminal with a conduit, up to 72 inches. Cables to the starter motor are exempt — the starting current would blow any sensible fuse.

WarningA fuse must not only detect the short-circuit current but also be able to interrupt it. This value is called the interrupting capacity. ANL and MRBF fuses are at around 10,000 A at 12 V, Class T at up to 20,000 A — and the value approximately halves when the voltage is doubled. With lithium battery banks with very low internal resistance, this is not a theoretical point.

Main fuse at the battery

Distance rules, designs, and interrupting capacity — and why the familiar ANL fuse reaches its limits with lithium.

Read more

Planning the switch panel

A switch panel is the place where design errors are most costly to fix because it is permanently installed. Planning follows four steps: group loads, provide a circuit for each group, determine cross-section and fuse for each circuit, and add a buffer.

Safety-relevant loads always get their own circuit — bilge pumps, navigation lights, and radio must not fail if a fuse blows somewhere else. For the same reason, ideally, they should not be behind a battery management system that can completely disconnect the battery bank in the event of a fault.

A reserve of 20 to 30 percent free circuits has proven effective. Retrofitting is labor-intensive with permanently installed panels, and something almost always gets added later.

Planning the switch panel: dividing circuits

From the load list to the finished panel: grouping, order of main switch and main fuse, reserves, and the questions that must be clarified before ordering.

Read more

Typical errors

  • Calculated single instead of double cable length. Results in half the cross-section and double the voltage drop.
  • Designed only based on current-carrying capacity. Over long distances, voltage drop is the stricter criterion, often by a multiple.
  • Fuse selected based on the device. It protects the cable; the nominal value must never exceed its capacity.
  • Main fuse in the switch panel instead of at the battery. The most dangerous cable then remains unprotected.
  • Interrupting capacity ignored. A fuse that cannot interrupt the short-circuit current will weld together.
  • Main switch before the fuse. This leaves the thickest piece of cable unprotected.
  • No reserve circuits. The cheapest part of the planning if it is included from the beginning.

Standards and regulations

The authoritative standard is ISO 13297:2020, which, as of this edition, covers DC systems up to 50 V and single-phase AC systems up to 250 V. Clause 5.5 requires a calculated voltage drop of no more than 10 percent of the nominal voltage, and clause 5.6 allows 3 percent for safety-relevant equipment. Clause 5.3 requires protective devices at the power source that interrupt overload currents before the insulation can be damaged. ISO 10133, which was previously responsible for the DC side, was withdrawn at the end of 2020.

In North America, ABYC E-11 regulates the same issues in greater detail and is also frequently used as a reference in Europe — especially for the distance rules for main fusing and for current-carrying capacity tables that distinguish between routing inside and outside of engine compartments. The minimum cross-section there is 16 AWG, which is approximately 1.3 mm².

FAQ

Frequently asked questions

What cable gauge do I need for 20 A at 5 meters?

At 12 V and a permissible voltage drop of 3 percent, approximately 10 mm² is required. The calculation uses double the cable length, i.e., 10 meters of conductor path. At 24 V, the value is halved to 6 mm² because the same percentage voltage drop means twice as many volts. For non-critical consumers with a 10 percent limit, 4 mm² is sufficient. The complete calculation method can be found in Calculate Cable Cross-Section.

The Line. A fuse prevents a cable from becoming so hot in the event of a fault that the insulation melts or a fire breaks out. The rated value therefore depends on the current carrying capacity of the cable, not on the appliance. Appliance protection is the responsibility of the appliance itself or of an additional, smaller fuse upstream.

So short as possible. ABYC E-11 specifies 175 millimeters from the connection point. If the cable is additionally routed in a protective conduit, up to 40 inches are permissible; with direct connection to the battery terminal with a protective conduit, up to 72 inches. The unprotected section before that is the real risk in case of a short circuit. More on this in Main Fuse at the Battery.

ISO 13297:2020 allows for up to 10 percent of the rated voltage for ordinary circuits. For safety-critical consumers — navigation lights, bilge blowers, bilge pumps — 3 percent applies. At 12 V, this is 1.2 and 0.36 volts respectively. The difference in cross-section is often more than double.

One for each consumer group that is to be switchable separately or fused separately - plus 20 to 30 percent reserve. Safety-relevant consumers always get their own circuit. Adding circuits later is time-consuming with permanently installed panels; the reserve is therefore the most economical part of the planning. Step-by-step planning can be found in Planning a Switch Panel.

Related to this topic

Matching products

philippi Engineering — Engineering department, philippi elektrische systeme GmbH

Written and technically reviewed by the engineering department of philippi elektrische systeme GmbH in Remseck am Neckar. If a standard or a product specification changes, the article is revised and the review date updated.

Development, manufacture and testing of on-board electrical components for over forty years

Erstellt · Zuletzt geprüft

Your case is not covered here?

Our team knows every component and usually replies on the same working day.