Safety and standards
Shore power on board.
Connect, protect and switch safely.
Shore power brings 230 V on board or into the living cabin, a voltage that is life-threatening in case of a fault. A safe installation therefore needs more than a plug and cable: residual current and overcurrent protection, a clean changeover between sources and, on boats, protection against galvanic corrosion. This page shows the path of shore power for yachts and expedition vehicles and leads to the right components.
230 V safely on board.
ISO 13297 standard for AC installations.
3 sources shore, generator, inverter.
Matching products. From our range.
The path of shore power
- Inlet and shore power cable: CEE inlet on the hull, deck or cabin wall, plus the cable to the shore or campsite pillar. See shore power inlets, plugs and cables.
- Shore power unit with RCBO: as close as possible to the inlet, with 30 mA residual current and overcurrent protection, often combined in one RCBO. See shore power units or, as a panel in the switchboard, the 230 V switchboard.
- Changeover switch: as soon as a generator or inverter is added, so only one source feeds in. See changeover switches for shore power, generator and inverter.
- Galvanic isolation (boats): galvanic isolator or isolation transformer against corrosion via the earth wire. See galvanic isolation.
- 230 V distribution: to the charger, water heater and sockets, protected by the circuit panels of the switchboard.
RCD and overcurrent protection
The residual current device (RCD) trips when current flows via a wrong path, such as through a person or water. The circuit breaker protects cables against overload and short circuit. An RCBO combines both. It belongs at the start of the installation, not further back in the distribution. For boats, DIN EN ISO 13297 sets the requirements for AC systems; for vehicles with living quarters, DIN VDE 0100-721 (IEC 60364-7-721) applies.
Changing over between shore power, generator and inverter
Two AC sources must never feed the system at the same time. A changeover switch ensures that only one source is connected. Manual cam switches are simple and robust; automatic units such as the LAU series switch by themselves as soon as shore power is present or the generator runs stably, and can integrate the inverter.
Galvanic corrosion on boats
Via the shore power earth, your boat is connected to other boats on the pontoon. Currents can flow that attack anodes, saildrive or propeller. A galvanic isolator in the earth wire blocks these small DC currents; an isolation transformer separates the on-board system completely from the shore grid. Vehicles have no underwater hull, so this does not apply to them.
Electric hook-up in an expedition vehicle
In an expedition or off-road vehicle the layout is similar: inlet on the cabin, hook-up cable to the campsite pillar, RCBO protection at the start of the 230 V system and a changeover switch when an inverter or generator is added. The Series 200 panels are available with the SKZ-MOBIL labelling set for vehicles. Campsites usually offer 16 A pillars, so 16 A is generally enough.
Frequently asked questions. Answered briefly.
Do I need an RCD for shore power?
Yes. A 30 mA residual current device belongs in every shore power installation, on boats and in expedition vehicles, as close as possible to the inlet, not further back in the distribution. It trips when current flows via a wrong path, such as through a person or water.
What is the difference between a galvanic isolator and an isolation transformer?
The galvanic isolator sits in the protective earth conductor and blocks small DC voltages there. They arise because your boat is connected to other boats on the pontoon via the protective earth, and they attack anodes, saildrive or propeller. The isolation transformer separates the on-board and shore networks completely and therefore offers the most comprehensive protection.
How do I switch between shore power and generator?
With a changeover switch that only ever lets one source onto the on-board network, because two AC sources must never be connected at the same time. Manual cam switches are simple and robust. Automatic changeover units switch by themselves as soon as shore power is present or the generator is running, and can include the inverter on request.
Where is the shore power unit installed?
As close as possible to where the shore power cable enters the boat or living cabin, so the unprotected cable is as short as possible. The shore power unit contains residual current and overcurrent protection (RCBO). Changeover and 230 V distribution to charger, water heater and sockets follow after it.
What is different about shore power in an expedition vehicle?
The layout is similar to a boat: inlet on the cabin, cable to the campsite pillar, RCBO at the start of the 230 V system and a changeover switch when an inverter or generator is added. Galvanic isolation is not needed because vehicles have no underwater hull. Campsites usually offer 16 A pillars.
Which standard applies to the 230 V system?
For boats DIN EN ISO 13297, which requires double-pole circuit protection and residual current protection of no more than 30 mA at the shore connection. For vehicles with living quarters DIN VDE 0100-721 applies. The 230 V installation should be carried out by a qualified electrician.
By Michael Kögel, Managing Director, philippi elektrische systeme GmbHPublished
Advice
Questions about your on-board network? We’ll plan it with you.
Describe your boat or vehicle to us and we will suggest the right components.
Academy
Read more. In the philippi Academy.
Connect shore power and secure
The shore power connection is where the onboard electrical system and the building installation meet — with all the associated risks. Residual...
Check shore power: reverse polarity and ground wire
A reversed shore power socket is only noticed in the event of a fault if there is no indicator. What can be...
Galvanic Corrosion: Causes and Countermeasures
At the dock, the galvanic cell does not stop at your own hull. How shore power connections involve other boats, how isolators...
ISO 13297: AC installations on board
Alternating current on board follows different rules than at home. Protective conductors, 30 mA residual current protection, double-pole disconnection, and the interlocking...