Manual Series 200 Switch Panels: Installation and Connection.

Series 200 distribution panels distribute and protect the 12/24 V on-board system. Each circuit has a switchable trip-free circuit breaker and an LED that goes out as soon as the breaker trips. Operation on DC 10–28 V, installation in dry interiors, usually at the chart table.

Manual edition: Series 200 distribution panels, version V1A, 16 pages (DE/EN). Download the manual as PDF (German/English) · Go to the Series 200 switch panels

Intended use

STV 200 series distribution panels distribute and protect the 12/24 V electrical system. Circuit breakers, control and display elements are mounted on the front panel. Each circuit is fitted with a switchable trip-free circuit breaker. The LED shows whether the circuit is switched on and ready; in the event of a short circuit the breaker switches off and the LED goes out.

Some models also have battery voltage or tank gauges; ammeters show the discharge current currently flowing. The circuits are labelled with the supplied circuit labels, which are stuck into the fields provided.

The panels operate only on extra-low DC voltage of 10–28 V. They are designed for use on yachts and in vehicles and may only be operated in enclosed spaces protected from rain, moisture, dust and condensation. Do not use where there is a risk of explosion from gas or dust; not suitable for outdoor use.

Safety instructions, liability, warranty

  • No modifications may be made to the unit, otherwise the CE mark becomes void.
  • Connection may only be carried out by qualified electricians.
  • Disconnect the battery cables before connecting. Observe the correct polarity of the batteries.
  • The built-in circuit breakers protect the cables to the loads. The loads themselves are protected by their own built-in fuses.

The installation and operating instructions are part of the delivery; keep them for later maintenance work and pass them on to any subsequent owner. philippi cannot monitor installation, operation and maintenance and therefore accepts no liability for damage resulting from incorrect installation or improper operation. The warranty is governed by philippi’s general terms and conditions.

Conformity: the units meet the requirements of Directive 2004/108/EC, confirmed by the CE mark. For disposal, observe local regulations and use the collection points for waste electrical equipment.

Scope of delivery, accessories, technical data

Scope of delivery: distribution panel, user manual, 1 sheet of self-adhesive SKZ circuit labels.

Accessory / spare part Designation
Circuit labels (1 sheet)SKZ-D, SKZ-GB, SKZ-NL, SKZ-FR, SKZ-ES, SKZ-DK, SKZ-Mobil (automotive)
Flat receptacles 6.3 mm, 1.5–2.5 mm²FSH 6,3/1,5-2,5
Circuit breaker, single-pole3130-F11B-H7T1-W29AG-10A (6–20 A)
Circuit breaker, double-pole3130-F15B-H7T1-W29AG-10A (6–16 A)
Operating voltageDC 10–28 V
Protection per circuit10 A (standard), alternatively 6, 16 or 20 A (20 A single-pole only)
Front panelAluminium, grey coated
Dimensionsdepending on model, see product page

Installation

Suitable locations are easily accessible places inside the boat, usually at the chart table. At least 15 cm of depth should be free behind the panel so that the wiring can be carried out carefully, clearly and safely. Install the panel so that it remains accessible from behind later for extensions, changes and repairs.

The mounting cut-out is about 10 mm smaller than the outer dimensions of the panel on each side. The panel is fastened through the four (six, depending on model) mounting holes with screws of your choice.

Warning: with cables that are too thin or contact resistance from corroded contacts, high currents can overheat cables and connections, which can catch fire. Observe the cable cross-section table and make sure connections are careful and tight.

Connecting to the battery

Connecting a Series 200 distribution panel to the battery with 35 A fuse, 6 mm² supply cable and ground busbar
  • The pre-wired red supply cables (+) of 6 mm² go to the positive terminal of the service battery. When extending them, the cross-section of the supply cable must not become smaller – risk of fire.
  • The supply cable is connected at the battery via a high-current fuse sized to the cable cross-section: at most 35 A for 6 mm², at most 50 A for 10 mm².
  • The cables to the loads go to the plug or screw contacts of the circuit breakers.
  • The black negative cable (−) goes to the negative terminal of the battery (preferably via a ground busbar). It supplies the LEDs and serves as the reference ground on panels with a voltmeter.

Overload and short circuit

If a circuit is overloaded or short-circuited, the circuit breaker trips, switches off the loads and the LED goes out. Once the cause has been eliminated, the breaker is reset by switching it on again.

Instruments and control switches

Terminal on the instrument Assignment
−Battery negative
+Power supply 12/24 V
BLighting voltage 12/24 V
STank sender input (10–180 ohms), e.g. TGT, TGW

Control switches required depending on equipment:

Control switch Switch positions Order no.
Voltmeter selector1-0-25 1808 1103
Tank sender selector1-25 1803 1102
Lighting switch0-15 1801 1102
FBH battery main switch(1)-0-(2)5 1808 1302
Bilge auto/manual switch1-0-25 1808 1103

A control switch can also be used to switch a tank monitor on and off, as well as the display lighting of tank and battery monitors. Make sure the power supply is fused. The exact wiring of the instruments is shown in the rear view in the PDF.

Navigation light monitoring

Wiring of the Series 200 navigation light monitoring: terminals E1–E6 and A1–A6 for bow, stern, anchor, tricolour and steaming lights

Connected are: port bow light, starboard bow light, stern light, anchor light, tricolour light, steaming light and negative.

  • Cable cross-section for the navigation lights: 2.5 mm² for conventional lamps, at least 1 mm² for LED navigation lights.
  • Bicolour bow light: connect to A1, jumper J1 stays in place (as delivered).
  • Two separate side lights (port/starboard): remove jumper J1.

Cable cross-section table

Single-core cable sizing according to “Germanischer Lloyd”:

Conductor cross-section Permissible load Recommended circuit breaker
1.5 mm²12 A10 A
2.5 mm²17 A16 A
4 mm²23 A20 A
6 mm²29 A25 A
10 mm²40 A35 A
16 mm²54 A50 A

For other lengths and voltages, use the cable cross-section calculator.

Ammeter and deep-discharge protection

Panels with an ammeter are available with an integrated shunt (input and output on the instrument) or with an external shunt; the supply cables are connected with at least 6 mm². Some panels have a remote control and display for a TSA deep-discharge protection. The circuit diagrams are in the PDF.