Manual LAE 220: Installing and Connecting the Shore Power Unit.

The LAE 220 shore power unit protects the onboard AC 230 V/50 Hz system with an RCBo 16 A residual current/miniature circuit breaker. It is designed for use inside the boat, not outdoors, and a mains indicator light shows the shore power connection. This page summarises the connection, wiring diagram and technical data from the operating manual.

Manual edition: Rev. 1C, August 2022, bilingual German and English.

The manual also applies to the Swiss version with 13 A: Manual for the LAE 220 CH.

Intended use

The LAE 220 shore power unit provides protection for the onboard AC 230 V/50 Hz system by means of an RCBo 16 A residual current/miniature circuit breaker (Swiss version CH: 13 A). It is designed for use inside the boat, not outdoors. The mains indicator light shows the shore power connection.

The electrical connection is made at the RCBo (RCD/MCB) for phase (L) and neutral (N) and, for the protective earth (PE), via a terminal strip in the housing of the LAE 220.

Connection and wiring diagram

Wiring diagram of the LAE 220 shore power unit with RCBo 16 A 30 mA, shore input, onboard output and protective earth terminal strip

Connect with a cable cross-section of at least 3 × 2.5 mm²; all conductors in the diagram are 2.5 mm².

Terminal Function according to the manual
1 Input phase L (shore)
N (input) Input neutral N (shore)
PE Protective earth, via terminal strip in the housing
2 Output phase L (onboard system)
N (output) Output neutral N (onboard system)

Indicator light H1 is connected at the input, in parallel with the AC cables. If the LAE 220 is installed more than 3 m from the shore power inlet plug, an additional miniature circuit breaker (MCB) must be installed close to the inlet; the manual names the LAE 205 for this purpose.

Installation notes

  • Work on low-voltage AC 230 V/50 Hz system components may only be carried out by authorised qualified electricians.
  • Make all connections to the shore power unit carefully and in accordance with the technical regulations (DIN EN ISO 13297).
  • The installation manual is part of the component delivery. Keep it in a safe place for later maintenance work and pass it on to any subsequent owners.

Technical data

Operating voltage AC 230 volts / 50 Hz
Input (shore connection) up to max. 3.6 kW (16 A)
Main protection RCBo (RCD/MCB) 16 A, 30 mA
LAE 220 CH version RCBo (RCD/MCB) 13 A, 30 mA
Dimensions W 80 × H 150 × D 97 mm
Protection rating IP 65

Disposal

Observe the applicable local regulations for disposal and use the collection points for waste electrical and electronic equipment.

More on this topic: Shore power on board · For questions about installation: Contact · Warranty and repair · All operating manuals