Manual LAE 205: Installing the Shore Power Circuit Breaker.
The LAE 205 shore power unit protects the onboard AC 230 V/50 Hz system with an MCB 16 A miniature circuit breaker (Swiss version 13 A). It must be installed close to the shore power inlet connector whenever the distance between the shore supply and the MCB is more than 3 m, and it is designed for use inside the boat. This page summarises the wiring diagram, installation and technical data from the installation manual.
Intended use and safety
The LAE 205 shore power unit provides circuit protection for the onboard AC 230 V/50 Hz system by means of an MCB 16 A miniature circuit breaker (Swiss version CH: 13 A). It must be installed close to the shore power inlet connector whenever the distance between the shore supply and the MCB is more than 3 m. It is designed for use inside the boat, not outdoors. The electrical connection is made at the MCB for phase (L) and neutral (N) and, for the protective earth (PE), via a terminal strip in the housing.
- Work on low-voltage AC 230 V/50 Hz system components may only be carried out by authorised qualified electricians.
- Make all connections carefully and in accordance with the technical regulations (DIN EN ISO 13297).
- The installation manual is part of the component delivery. Keep it in a safe place for later maintenance work and pass it on to any subsequent owners.
General notes on AC products: Safety instructions for AC 230 V products (PDF, German).
Connection and wiring diagram

Cable cross-section at least 3 × 2.5 mm², all conductors in the diagram are 2.5 mm².
| Terminal | Input (shore, AC IN Shore) | Output (onboard system, AC OUT) |
|---|---|---|
| 1 / 2 | 1: Phase L | 2: Phase L |
| N | Neutral N | Neutral N |
| PE | Protective earth | Protective earth |
Technical data
| Operating voltage | AC 230 volts / 50 Hz |
| Input terminal 1 | Shore connection up to max. 3.6 kW (16 A) |
| Main protection | MCB 16 A, 30 mA |
| LAE 205 CH version | MCB 13 A, 30 mA |
| Dimensions | W 80 × H 150 × D 97 mm |
| Protection rating | IP 65 |
Disposal
For disposal, local regulations apply; use the collection points for waste electrical and electronic equipment.