Manual LAE 230: Installing the Shore Power Unit with Two Circuits.
The LAE 230 shore power unit protects the onboard AC 230 V/50 Hz system with an RCBo 16 A residual current/miniature circuit breaker and two MCB 10 A miniature circuit breakers. It is designed for use inside the boat, not outdoors, and a mains indicator light shows the shore power connection. This page summarises the connection, wiring diagram and technical data from the operating manual.
Intended use
The LAE 230 shore power unit provides protection for the onboard AC 230 V/50 Hz system by means of an RCBo 16 A residual current/miniature circuit breaker and two MCB 10 A miniature circuit breakers. It is designed for use inside the boat, not outdoors. The mains indicator light shows the shore power connection.
The electrical input connection is made at the RCBo (RCD/MCB) for phase (L) and neutral (N) and, for the protective earth (PE), via a terminal strip in the housing of the LAE 230. On the output side, the connection is made at the MCB miniature circuit breakers.
Connection and wiring diagram

| Connection | Function according to the manual | Cable cross-section |
|---|---|---|
| RCBo 2 | Input phase L | min. 3 × 2.5 mm² |
| RCBo N | Input neutral N | min. 3 × 2.5 mm² |
| PE | Protective earth via common terminal | – |
| MCB-F2 2 | Output 1 phase L | min. 3 × 1.5 mm² |
| MCB-F2 4 | Output 1 neutral N | min. 3 × 1.5 mm² |
| MCB-F3 2 | Output 2 phase L | min. 3 × 1.5 mm² |
| MCB-F3 4 | Output 2 neutral N | min. 3 × 1.5 mm² |
The protective earth (PE) of the input and of the outputs is connected via the common terminal. Indicator light H1 is connected at the input, in parallel with the AC cables. If the unit is installed more than 3 m from the shore power inlet plug, an additional miniature circuit breaker (MCB) must be installed close to the inlet; the manual names the LAE 205 for this purpose.
Installation notes
- Work on low-voltage AC 230 V/50 Hz system components may only be carried out by authorised qualified electricians.
- Make all connections to the shore power unit carefully and in accordance with the technical regulations (DIN EN ISO 13297).
- The installation manual is part of the component delivery. Keep it in a safe place for later maintenance work and pass it on to any subsequent owners.
Technical data
| Operating voltage | AC 230 volts / 50 Hz |
| Input terminal 2 | Shore connection up to max. 3.6 kW (16 A) |
| Main protection | RCBo (RCD/MCB) 16 A, 30 mA, 2 × MCB 10 A |
| Dimensions | W 160 × H 200 × D 115 mm |
| Protection rating | IP 65 |
Disposal
Observe the applicable local regulations for disposal and use the collection points for waste electrical and electronic equipment.
More on this topic: Shore power on board · For questions about installation: Contact · Warranty and repair · All operating manuals
Manual didn't help? We are happy to help.
Contact